Home Products Blog Contact Catalog Company 0216 364 02 10
UAx300 Modbus and SNMP Gateway - uax300-modbus-snmp-gateway.webp

UAx300 Modbus and SNMP Gateway

HVAC - INDUSTRIAL PROTOCOL GATEWAY

What Is an OPC UA and BACnet IP Gateway for Modbus and SNMP?

MeasuresPhere UAx300 is an industrial protocol gateway that collects data from field devices using Modbus RTU, Modbus TCP/IP, and SNMP protocols and transfers this data to higher-level systems via its OPC UA Server and BACnet IP interfaces.

While collecting field data through four isolated RS485 ports and an Ethernet LAN connection, the device also enables OPC UA and BACnet IP clients to access data locally or remotely through a dedicated WAN Ethernet port and built-in 4G LTE modem.

OPC UA AND BACnet IP GATEWAY FOR MODBUS AND SNMP

A key solution for your HVAC and BMS projects.

The MeasuresPhere Protocol Gateway collects field data via Modbus RTU, Modbus TCP/IP and SNMP and makes this data available to higher-level systems through OPC UA Server and BACnet IP. It gathers data from field devices through four isolated RS485 ports and an Ethernet LAN connection, while a dedicated WAN Ethernet port and built-in 4G LTE modem provide data access for both local and remote systems.

FIELD & PLC SIDE
Collect field data through multiple ports

Connect Modbus RTU devices through four independent and isolated RS485 ports, while Modbus TCP/IP and SNMP devices can be connected through the Ethernet LAN port, all within a single gateway.

Modbus RTU Modbus TCP/IP 4 x RS485 for Modbus RTU Ethernet port for Modbus TCP and SNMP
OT / IT SIDE
Publish data via OPC UA and BACnet IP

Make collected field data available to SCADA, BMS and other client systems via OPC UA Server or BACnet IP. Data can be accessed locally through the WAN Ethernet connection or remotely through the built-in 4G LTE modem.

OPC UA Server + HA BACnet IP Ethernet or 4G LTE for OPC UA and BACnet connectivity
MeasuresPhere UAx300 Modbus SNMP OPC UA BACnet Gateway
Advanced Data Access and Security for OPC UA Server
The built-in OPC UA Server provides access to historical data via OPC UA with Historical Access (HA) support. Certificate upload and certificate management are also supported for OPC UA connections, enabling secure client-server communication.
HARDWARE · SPECIFICATIONS

Powerful and flexible hardware for industrial connectivity.

MeasuresPhere UAx300 provides an industrial edge gateway hardware platform designed for continuous operation between field devices and higher-level systems, featuring four isolated serial communication ports, dedicated LAN and WAN Ethernet interfaces, 4G LTE connectivity, a wide DC power supply range and a rugged metal enclosure.

SERIAL
4× Isolated Serial Ports
2× RS485 + 2× RS232/485
LAN
1× 10/100 Mbps
Ethernet LAN
WAN
1× 10/100 Mbps
Ethernet WAN
4G LTE GSM
Built-in GSM Modem
Micro-SIM · SMA
System
Processor Armv7 Quad-Core Cortex-A9 · 1.4 GHz
RAM 512 MB DDR3 · 1 GB option
Internal Storage 8 GB eMMC
Storage Expansion TF / microSD · up to 128 GB
Communication
Isolated Serial Ports 2× RS485 + 2× RS232/485
Serial Port Protection 4 kV Surge · ESD ±15 kV
LAN Ethernet 1× Auto-Sensing 10/100 Mbps
WAN Ethernet 1× Auto-Sensing 10/100 Mbps
Ethernet Protection 2 kV Surge · ESD ±15 kV
GSM Modem Quectel EC25 ·

DOWNLOADS

You can view and download the technical documentation for the MeasuresPhere UAx300 protocol gateway using the link below.

Demo software downloads will be activated by filling out the form.
Now you can download the following software suitable for you. After clicking the button, the download link of the software will be sent to your e-mail address.
WhatsApp
×
Demo of this product is available.

You can download the free demo to try this product. To access the download form click.